Certification11 min read12 February 2026

Fire protection with TAVINOX PRESS

Certification, PN 16/12.5 bar pressures and the installation requirements in fire-fighting systems.

Certification for fire protection pipework

The TAVINOX PRESS system is certified for fire protection pipework by PAVUS, the Czech fire safety certification body, and by VdS (Verband der Sachversicherer). The certification covers:

  • Fittings OD 22–108 mm
  • OK02 (EPDM) O-rings certified to VdS
  • TR10MM (316L) and TR60MM (304L) tubes

Important: the PR10FF and NS10FRP fittings are NOT certified for fire protection pipework.

Video on this topic

From the TAVINOX Academy series, filmed on a real tube.

Episode #3: Pressing Ø 76.1–108 mm – single and double pressing

All videos in the Video Academy

Operating pressures for fire protection applications

The pressures permitted in fire protection pipework are those certified by PAVUS:

  • OD 15–88.9 mm (DN20–DN80): 16 bar (max. operating pressure)
  • OD 108 mm (DN100): 12.5 bar (max. operating pressure)

The smaller sizes therefore match the nominal pressure of the system, PN 16; at OD 108 mm the permissible pressure is reduced to 12.5 bar. Fire protection pipework is also subject to stricter pressing requirements — the minimum forces are given below.

Minimum pressing forces — fire protection pipework

STRICTER pressing force requirements apply to fire protection pipework:

  • OD 22–54 mm: at least 32 kN — a single press
  • OD 76.1–108 mm: at least 65 kN — DOUBLE pressing

Double pressing means that every joint is pressed twice — once from each side. This is mandatory for the large diameters in fire protection pipework.

Installation requirements

Requirements specific to fire protection pipework:

1

All joints must be accessible for visual inspection

2

The pipework must be marked as fire protection pipework (red identification)

3

Supports must be made of non-combustible materials

4

Penetrations through floors and walls must be closed with a fire-stopping seal

5

Pressure test: 1.5× the operating pressure, min. 2 hours

6

The pressure test report must form part of the handover documentation